This paper reports the results of experimental work carried out on a micro-tubular solid oxide fuel cell tri-generation systemthat uses the waste heat from the fuel cell for dehumidification and cooling though the integration of an open cycle liquid desiccant dehumidification and cooling system. The experimental results demonstrate regeneration of the potassium formate solution using the thermal output from the SOFC in the first of its kind tri-generation system. Optimisation has shown that a 2.2L.min-1 regenerator desiccant volumetric flow facilitates best performance.When integrated with the micro-SOFC, the open cycle desiccant system demonstrates a COP of approaching 0.7, an encouraging value for a waste heat driven cooling system of this capacity. A tri-generation performance analysis is presented which serves to demonstrate the novel system operating in a building. The system achieved an electrical efficiency of 11% and regeneration efficiency of approximately 37%. The electrical efficiency is lower than that predicted by the company supplying the micro-tubular SOFC, because the unit suffered sulphur poisoning during preliminary tests. The electrical power output decreased from 250W to 150W, which reduced the electrical efficiency from around 18% to 11% and the overall efficiency from approximately 45% to just over 37%. Low temperature (33-36°C) regeneration was demonstrated.
Citation
Worall, M., Elmer, T., Riffat, S., Wu, S., & Du, S. (2017). An experimental investigation of a micro-tubular SOFC membrane-separated liquid desiccant dehumidification and cooling tri-generation system. Applied Thermal Engineering, 120, https://doi.org/10.1016/j.applthermaleng.2017.03.032
Journal Article Type | Article |
---|---|
Acceptance Date | Mar 9, 2017 |
Online Publication Date | Mar 21, 2017 |
Publication Date | Jun 25, 2017 |
Deposit Date | Mar 22, 2017 |
Publicly Available Date | Mar 22, 2017 |
Journal | Applied Thermal Engineering |
Print ISSN | 1359-4311 |
Electronic ISSN | 1873-5606 |
Publisher | Elsevier |
Peer Reviewed | Peer Reviewed |
Volume | 120 |
DOI | https://doi.org/10.1016/j.applthermaleng.2017.03.032 |
Keywords | fuel cell, SOFC, microtubular, tri-generation, desiccant, dehumidification |
Public URL | https://nottingham-repository.worktribe.com/output/867838 |
Publisher URL | http://www.sciencedirect.com/science/article/pii/S1359431117316095 |
Contract Date | Mar 22, 2017 |
Files
Paper ATE_2016_10036 _microSOFC trigen MW.pdf
(920 Kb)
PDF
Copyright Statement
Copyright information regarding this work can be found at the following address: http://creativecommons.org/licenses/by-nc-nd/4.0
You might also like
Downloadable Citations
About Repository@Nottingham
Administrator e-mail: discovery-access-systems@nottingham.ac.uk
This application uses the following open-source libraries:
SheetJS Community Edition
Apache License Version 2.0 (http://www.apache.org/licenses/)
PDF.js
Apache License Version 2.0 (http://www.apache.org/licenses/)
Font Awesome
SIL OFL 1.1 (http://scripts.sil.org/OFL)
MIT License (http://opensource.org/licenses/mit-license.html)
CC BY 3.0 ( http://creativecommons.org/licenses/by/3.0/)
Powered by Worktribe © 2025
Advanced Search