Experimental study on the measurement of building infiltration and air leakage rate (at 4 and 50 Pa) by means of tracer gas methods, blower door and the novel pulse technique in a detached UK home

Vega Pasos, Alan; Zheng, Xiaofeng; Sougkakis, Vasileios; Gillott, Mark; Meulemans, Johann; Samin, Olivier; Alzetto, Florent; Smith, Luke; Jackson, Stephen; Wood, Christopher J.

Authors

Alan Vega Pasos

XIAOFENG ZHENG Xiaofeng.Zheng@nottingham.ac.uk
Assistant Professor - Building Services

Vasileios Sougkakis

MARK GILLOTT MARK.GILLOTT@NOTTINGHAM.AC.UK
Professor of Sustainable Building Design

Johann Meulemans

Olivier Samin

Florent Alzetto

Luke Smith

Stephen Jackson



Abstract

Air infiltration contributes to a heat loss typically representing up to one third of the heating demand of a building. The building airtightness, also quantified as air leakage, is the fundamental building property that impacts infiltration. The steady (de)pressurization method (blower door) is the widely accepted standard process for measuring building air leakage. However, this method requires the enclosure to be pressurised to a typical range of 10-60 Pa, which is not physically representative of the pressures experienced by buildings under natural conditions. The Pulse technique is a novel alternative method, which measures air leakage at low pressures; quoting it at a reference pressure of 4 Pa. An experiment was designed to test the leakage characteristics of a detached house in the UK and compare them with the infiltration rate; which were measured by tracer gas techniques, utilising the decay method. The blower door and Pulse tests were both performed multiple times during a six week period to cover a range of different environmental conditions. Initial results have shown that there might be correlation between the infiltration rate and air leakage at 4 Pa and 50 Pa. It was concluded that Pulse technique’s results induce less uncertainty when predicting air infiltration. Further experimental testing is required to be carried out in a range of properties to investigate how this conclusion stands and how the results given by existing infiltration models compare with the experimentally obtained infiltration rate.

Citation

Vega Pasos, A., Zheng, X., Sougkakis, V., Gillott, M., Meulemans, J., Samin, O., …Wood, C. J. (2018). Experimental study on the measurement of building infiltration and air leakage rate (at 4 and 50 Pa) by means of tracer gas methods, blower door and the novel pulse technique in a detached UK home. In Smart Ventilation for buildings (972-981)

Conference Name 39th AIVC - 7th TightVent & 5th venticool Conference
Conference Location Antibes Juan-Les-Pins, France
Start Date Sep 18, 2018
End Date Sep 19, 2018
Acceptance Date Jul 1, 2018
Online Publication Date Sep 18, 2018
Publication Date Sep 18, 2018
Deposit Date Nov 22, 2018
Publicly Available Date Nov 27, 2018
Pages 972-981
Book Title Smart Ventilation for buildings
Keywords Air infiltration, air leakage, tracer gas, pulse, blower door
Public URL https://nottingham-repository.worktribe.com/output/1192004

Files





You might also like



Downloadable Citations