A Fast Diagnosis Method for Both IGBT Faults and Current Sensor Faults in Grid-Tied Three-Phase Inverters With Two Current Sensors
(2019)
Journal Article
Li, Z., Wheeler, P., Watson, A., Costabeber, A., Wang, B., Ren, Y., …Ma, H. (2020). A Fast Diagnosis Method for Both IGBT Faults and Current Sensor Faults in Grid-Tied Three-Phase Inverters With Two Current Sensors. IEEE Transactions on Power Electronics, 35(5), 5267-5278. https://doi.org/10.1109/tpel.2019.2946692
© 1986-2012 IEEE. This article considers fault detection in the case of a three-phase three-wire (3P3W) inverter, when only two current sensors are used to save cost or due to a faulty current sensor. With two current sensors, there is no current met... Read More about A Fast Diagnosis Method for Both IGBT Faults and Current Sensor Faults in Grid-Tied Three-Phase Inverters With Two Current Sensors.