Dr JOHN CALAUTIT JOHN.CALAUTIT1@NOTTINGHAM.AC.UK
ASSOCIATE PROFESSOR
Climatic analysis of a passive cooling technology for the built environment in hot countries
Calautit, John Kaiser; Hughes, Ben Richard; Nasir, Diana S.N.M.
Authors
Ben Richard Hughes
Diana S.N.M. Nasir
Abstract
© 2016 Elsevier Ltd The aim of this work was to determine the ventilation and cooling potential of a passive cooling windcatcher operating under hot climatic conditions by replicating the monthly wind velocity, wind direction, temperature and relative humidity (RH) observed in a hot-desert city. The city of Ras-Al-Khaimah (RAK), UAE was used as the location of the case-study and available climatic data was used as inlet boundary conditions for the numerical analysis. The study employed the CFD code FLUENT 14.5 with the standard k–ε model to conduct the steady-state RANS simulation. The windcatcher model was incorporated to a 3 × 3 × 3 m3 test room model, which was identical to the one used in the field test. Unlike most numerical simulation of windcatchers, the work will simulate wind flows found in sub-urban environment. The numerical model provided detailed analysis of the pressure, airflow and temperature distributions inside the windcatcher and test room model. Temperature and velocity profiles indicated an induced, cooler airflow inside the room; outside air was cooled from 38 °C to 26–28 °C, while the average induced airflow speed was 0.59 m/s (15% lower compared to a windcatcher w/out heat pipes). Field testing measurements were carried out in the Jazira Hamra area of RAK during the month of September. The test demonstrated the positive effect of the integration of heat pipes on the cooling performance but also highlighted several issues. The comparison between the measured and predicted supply temperatures were in good agreement, with an average error of 3.15%.
Citation
Calautit, J. K., Hughes, B. R., & Nasir, D. S. (2017). Climatic analysis of a passive cooling technology for the built environment in hot countries. Applied Energy, 186, 321-335. https://doi.org/10.1016/j.apenergy.2016.05.096
Journal Article Type | Article |
---|---|
Acceptance Date | May 14, 2016 |
Online Publication Date | May 24, 2016 |
Publication Date | Jan 15, 2017 |
Deposit Date | Sep 19, 2017 |
Publicly Available Date | Sep 19, 2017 |
Journal | Applied Energy |
Print ISSN | 0306-2619 |
Electronic ISSN | 0306-2619 |
Publisher | Elsevier |
Peer Reviewed | Peer Reviewed |
Volume | 186 |
Pages | 321-335 |
DOI | https://doi.org/10.1016/j.apenergy.2016.05.096 |
Keywords | Building, Computational modelling, Field testing, Heat pipe, Natural ventilation |
Public URL | https://nottingham-repository.worktribe.com/output/788765 |
Publisher URL | http://www.sciencedirect.com/science/article/pii/S0306261916306900 |
Contract Date | Sep 19, 2017 |
Files
Climatic analysis of a passive cooling technology for the built environment in hot countries.pdf
(2.2 Mb)
PDF
Copyright Statement
Copyright information regarding this work can be found at the following address: http://creativecommons.org/licenses/by-nc-nd/4.0
You might also like
A Review of Thermochemical Energy Storage Systems for District Heating in the UK
(2024)
Journal Article
Downloadable Citations
About Repository@Nottingham
Administrator e-mail: discovery-access-systems@nottingham.ac.uk
This application uses the following open-source libraries:
SheetJS Community Edition
Apache License Version 2.0 (http://www.apache.org/licenses/)
PDF.js
Apache License Version 2.0 (http://www.apache.org/licenses/)
Font Awesome
SIL OFL 1.1 (http://scripts.sil.org/OFL)
MIT License (http://opensource.org/licenses/mit-license.html)
CC BY 3.0 ( http://creativecommons.org/licenses/by/3.0/)
Powered by Worktribe © 2024
Advanced Search